Brand Name : UNI-CABLES
Model Number : FR 1KV
Certification : ISO9001
Place of Origin : CHINA
MOQ : 500 Meters
Price : Negotiable
Supply Ability : 70000 Meters per Week
Delivery Time : 15-20 working days
Packaging Details : 500 Meters per wooden reel
Conductor : Class 2 stranded copper conductor
Separator : Mica/glass fire barrier tape
Insulation : XLPE (Cross-Linked Polyethylene)
Bedding : LSZH (Low Smoke Zero Halogen)
Sheath : LSZH (Low Smoke Zero Halogen)
Operating Temperature : -10°C to +90°C
BS7846 CU/XLPE/SWA/PVC Fire Performance Cable LSZH Fire Resistance Cable
Application
These cables offer the advantages of an armoured 600/1000V rated, zero halogen, low smoke cable with circuit integrity. They are intended for use in installations where vital circuits are required to continue operation in the event of the outbreak of fire. It is particularly suited for use in public buildings and constructions (such as hospitals, theatres, shopping developments, tunnels, mass transit railways, oil & petrochemical plants, power stations and computer installations) where the danger to life, equipment and structures may be greatly increased in the event of a power failure due to fire.
Standard
BS 7846
Specifications
Voltage Rating : 600 / 1000V
Operating Temperature : -40°C to + 90°C
(The cable should not be flexed when either the ambient or cable temperature is below 0°C)
Minimum Bending Radius : 12 x overall diameter of cable
Cable Construction
Construction :Plain annealed stranded copper conductors.
Conductor : For sizes up to and including 16mm² are offered in circular . Shaped conductors are offered from 25 mm² and onwards.
Insulation : Mica (fire – resistant) tapes, covered by an extruded layer of cross – linked polyethylene.
Bedding :An extruded layer of thermoplastic zero halogen, low smoke compound.
Armour :Single layer of galvanized steel wires.
Sheath : Thermoplastic zero halogen, low smoke, compound.
Zero halogen, low Smoke cable with standard copper conductors.
DIMENSIONS
Number. of Cores | Nominal Cross Sectional Area (Sq. mm) | Insulation Thickness (mm) | Nominal Armour Wire Diameter (mm) | Approx. Diameter Under Armour (mm) | Approx. Overall Diameter (mm) | Approx. Cable Weight (kg/km) | Max. DC Conductor Resistance at 20oC (O/km) | Max. AC Conductor Resistance at 90oC (O/km) |
4 | 1.5* | 0.6 | 0.9 | 9 | 13.5 | 423 | 12.1 | 15.428 |
4 | 1.5* | 0.6 | 0.9 | 10 | 14.8 | 522 | 12.1 | 15.428 |
4 | 2.5* | 0.7 | 0.9 | 11.5 | 16 | 618 | 7.41 | 9.448 |
4 | 4* | 0.7 | 0.9 | 13 | 17.8 | 725 | 4.61 | 5.878 |
4 | 6* | 0.7 | 1.25 | 14.5 | 20 | 985 | 3.08 | 3.927 |
4 | 10* | 0.7 | 1.25 | 16.5 | 22 | 1255 | 1.83 | 2.333 |
4 | 16 | 0.7 | 1.25 | 19 | 24.5 | 1635 | 1.15 | 1.466 |
4 | 25 | 0.9 | 1.6 | 22 | 28.5 | 2145 | 0.727 | 0.927 |
4 | 35 | 0.9 | 1.6 | 24.5 | 31.5 | 2645 | 0.524 | 0.668 |
4 | 50 | 1 | 1.6 | 26 | 33.2 | 3103 | 0.387 | 0.494 |
4 | 70 | 1.1 | 2 | 30.5 | 39.2 | 4405 | 0.268 | 0.342 |
4 | 95 | 1.1 | 2 | 34.5 | 43.2 | 5653 | 0.193 | 0.247 |
4 | 120 | 1.2 | 2.5 | 38.5 | 48.6 | 7252 | 0.153 | 0.196 |
4 | 150 | 1.4 | 2.5 | 42.5 | 53 | 8553 | 0.124 | 0.16 |
4 | 185 | 1.6 | 2.5 | 47.5 | 58 | 10304 | 0.0991 | 0.128 |
4 | 240 | 1.7 | 2.5 | 53.5 | 64.5 | 12895 | 0.0754 | 0.099 |
4 | 300 | 1.8 | 2.5 | 59 | 70.3 | 15545 | 0.0601 | 0.08 |
4 | 400 | 2 | 3.15 | 66.5 | 79.8 | 20245 | 0.047 | 0.064 |
* Class 2 stranded circular (non compacted) conductor.
![]() |